Single phase two wire electricity meter


MTR-EKC2 Single phase two wire Din Rail energy meter

£44.80

The MTR-EKC1 is a single phase two wire Din Rail energy meter with either a register or LCD display that ensures a high accuracy class (Class1).

In stock

Product Code: MTR-EKC1

Category:

Product Description

The MTR-EKC1 is a single phase two wire Din Rail energy meter with either a register or LCD display that ensures a high accuracy class (Class1).

CONSUMPTION INDICATION
There is a red LED which is used as indicating power consumption in the front panel of MTR-EKC1. When consumption happens, the LED will flash. The more quickly LED flashes, the more consumption there is. For this LED, the flash rate is indicated per kWh on the front panel

REVERSE INDICATION
There is a red LED which is used as indicating current reverse in the front panel.

READING THE METER.
The MTR-EKC1 energy meter is equipped with a 5+1 register. Five integers are marked with black colour
and one decimal is marked with red. The MTR-EKC1 energy meter is equipped with 6+1 or 5+2 LCD display. Which is used as recording consumption and can’t be reset to zero. The number
system is based on units of 10. And unit is kWh.

PULSE OUTPUT
The MTR-EKC1 DIN rail energy meter is equipped with a pulse output which is fully separated from the inside circuit. That generates pulses in proportion to the measured energy for accuracy testing. The pulse output is a polarity dependant, passive transistor output requiring an external voltage source for correct operation. For this external voltage source, the voltage (Ui) should is 5-27V DC, and the maximum input current (Imax) is 27mA DC. To connect the impulse output, connect 5-27V DC
to connector 6 (anode), and the signal wire (S) to connector 5 (cathode). The meter has an 1600 pulses / KWh output.

 

Specifications

Weight 0.2 kg
Dimensions 65 × 76 × 130 mm
Operating humidity

≤ 75%

Storage humidity

≤ 95%

Operating temperature

-10°C – +50°C

Storage temperature

-30°C ~ +70°C

International standard

IEC 62053-21

Protection against penetration of dust and water

IP51

Nominal voltage (UN)

230V AC

Operational voltage

0.7 – 1.3Un

Insulation capabilities: - AC voltage withstand - Impulse voltage withstand

2KV for 1 minute
6KV – 1.2μS waveform

Basic current (Ib)

1.5A/5A/10A

Maximum rated current (Imax)

6A/60A/100A

Operational current range

0.4% Ib- Imax

Over current withstand

30Imax for 0.01s

Operational frequency range

50 ~ 60Hz ±10%

Internal power consumption

30Imax for 0.01s

Test output flash rate (RED LED)

12800/3200/1600imp/kWh

Pulse output rate (pins 5 & 6)

12800/3200/1600imp/kWh

Reverse indicator (RED LED)

Current reverse

Consumption indicator (RED LED)

Flashing at load running